FLT93L Flow Switch
SKU: FLT93L
The FLT93L inline type FlexSwitch for flow and temperature monitoring represents the first true technological breakthrough in thermal technology in over a decade. FCI is the only thermal manufacturer providing temperature compensation to ensure set point accuracy for process temperatures that vary up to ± 100°F. The FLT93L is easily field-configured or factory preset, providing unparalleled flexibility, accuracy and stability for all multiple process sensing and switching requirements.
Product Details
For Flow Service - Setpoint Range:
Water-based Liquids:
0.015 to 50 cc/sec
Hydrocarbon-based Liquids:
0.033 to 110 cc/sec
Air/Gas:
0.6 to 20,000 cc/sec
Accuracy: (whichever reading is higher)
Liquids: ± 0.5% reading or ± 0.04 fps [± 0.012 mps]
Gases: ± 0.5% reading or ± 2 sfps [± 0.06 nmps]
For Temperature Service:
Accuracy: ± 2° F [±1° C]
Repeatability: ± 1° F [± 0.6° C]
Response Time: As low as 0.5 seconds.
Enclosure: NEMA 4X/IP66 Rated. Standard: Polyester power coated aluminum, with single 1" NPT conduit port. Optional: Stainless steel. Optional: Dual-conduit port, aluminum with 1/2" NPT or M20 metric conduit ports.
Compliances and Agency Approvals: FM, FMc, ATEX, IECEx, EAC/TR CU, Inmetro, EQM/ECAS. CE mark. PED, CRN. (UKCA, UKEX pending)
Meets EC directives for EMC and LVD. Probe complies with Canadian Electrical code requirements of ANSI/ISA 12.27.01-2011 as a single seal device.
| FM/FMc: |
| ||
| ATEX: | Integral: II 2 G Ex db IIC T4…T2 Gb II 2 D Ex tb IIIC T135°C…T300°C Db Remote enclosure + electronics: II 2 G Ex db IIC T6 Gb II 2 D Ex tb IIIC T85°C Db Local enclosure + sensor II 2 G Ex db IIC T4…T1 Gb II 2 D Ex tb IIIC T135°C…T345°C Db Pigtail version II 2 G Ex db IIC T4…T3 Gb II 2 D Ex tb IIIC T135°C…T200°C Db | ||
| IECEx: (EQM/ECAS) | Integral: Ex db IIC T4…T2 Gb Ex tb IIIC T135°C…T300°C Db Remote enclosure + electronics: Ex db IIC T6 Gb Ex tb IIIC T85°C Db Local enclosure + sensor Ex db IIC T4…T1 Gb Ex tb IIIC T135°C…T345°C Db Pigtail version Ex db IIC T4…T3 Gb Ex tb IIIC T135°C…T200°C Db |
Optional N.I.S.T. Flow Calibration Services
Factory N.I.S.T. calibration in air or water is available as an option for customer specified setpoint(s) or a flow curve based on the media ranges specified above.
Flow Element
Materials of Construction: All welded 316L stainless steel for all wetted surfaces.
Process Connection:
Standard: 1 inch male NPT or 0.75 inch female NPT at tee inlet and outlet
Optional: Flanges
Inline Tee Length: 3.375 inch [86 mm]
Operating Temperature:
Standard: -40° to +350° F [-40° to +177° C]
Optional: -100° to +500° F [-73° to +260° C]
Operating Pressure: To 3500 psig [240 bar(g)]
Control Circuit
Operating Temperature: -40° to +140° F [-40° to +60° C]
Universal AC/DC supply. Input terminals and jumpers on circut board select specific power.
| AC | 108-132V | 13W, 100mA max. |
| AC | 207-253V* | 14W, 50mA max. |
| AC | 18-28V | 7W, 230mA max. |
| DC | 21-30V | 7W, 230mA max. |
* AC mains preset by factory: FM & FMc as 108-132 Vac; All others as 207-240 Vac
Relay Contacts: Field configurable dual SPDT or single DPDT rated 6 amps at 115 Vac, 240 Vac or 24 Vdc. Hermetically sealed relays are available as an option.
Output Signal: Analog DC voltage related to flow or level/interface signal and proportional to temperature.
Electrical Connection: 1 inch female NPT
Remote Configuration: Available as an option with customer specified interconnecting cable length.
Quick Access